Skip to main content

FX

Fan Coil Units
Prospectus
Product Category
Terminal Units
FX Series Fan Coil Unit

Type FX - VA / VB / VC (vertical floor / wall version, with cabinet)
Type FX - CA / CB / CC / CD (vertical concealed version, without cabinet)
Type FX - HA / HB / HC (horizontal ceiling version, with cabinet)
Type FX - CH / CK / CS (horizontal concealed version, without cabinet)

FX series is available in 14 sizes, in 13 different versions, with 1 or 2 coils
(for a 2-pipe or a 4-pipe water system).

Nominal cooling capacity:
1,5 kW – 10,71 kW (3 Rows, 2-pipe system)
1,45 kW – 10,51 kW (3+1 Rows, 4-pipe system)
at operational conditions:
entering air temperature: 27⁰C DB / 19⁰C WB,
inlet / outlet water temperature: 7 / 12⁰C,
at max (3rd) fan speed, with free air flow (ESP=0 Pa).

Nominal heating capacity:
3,74 kW - 23,2 kW (3 Rows, 2-pipe system)
1,88 kW – 11,2 kW (3+1 Rows, 4-pipe system)
at operational conditions:
entering air temperature: 20⁰C,
inlet / outlet water temperature: 70 / 60⁰C,
at max (3rd) fan speed, with free air flow (ESP=0 Pa).